Breaker Interrupting Ratings (AIC) in Legacy MCC Buckets
UL interrupting ratings, kA RMS symmetrical, for the frames that actually live in 20 to 50 year old lineups. Compiled from manufacturer catalog documents, cited under each table.
Every fault-current study, arc-flash label, and bucket replacement runs into the same question: what can the breaker in that unit actually interrupt? The frames in legacy MCC buckets span decades of catalogs, several corporate acquisitions, and a naming system where one letter changes the interrupting rating by a factor of three. The ratings below are UL interrupting capacities in kA RMS symmetrical, compiled from the manufacturer documents cited under each table.
How to read the families: each manufacturer tiers the same physical frame by interrupting capacity. Square D encodes the tier in the second letter (FAL standard, FHL high, FCL extra-high, FIL current-limiting). Eaton/Cutler-Hammer prefixes the F-frame (FD standard, HFD high, FDC extra-high). GE uses TED to THED, TFJ/TFK to THFK, TJK to THJK. Siemens steps ED4/ED6 to HED4 to CED6. Two breakers that look identical in the bucket can differ by 80 kA of interrupting capacity, which is why the study needs the exact catalog number, not the frame name.
Square D: F-frame (100 A) and K-frame (250 A)
| Type | Amps | Max voltage | AIC @ 240 V | AIC @ 480 V | AIC @ 600 V |
|---|---|---|---|---|---|
| FAL (240 V cat.) | 15-100 A | 240 V | 10 kA | not rated | not rated |
| FAL (FAL34xxx) | 15-100 A | 480 V | 25 kA | 18 kA | not rated |
| FAL (FAL36xxx) | 15-100 A | 600 V | 25 kA | 18 kA | 14 kA |
| FHL | 15-100 A | 600 V | 65 kA | 25 kA | 18 kA |
| FCL | 15-100 A | 480 V | 100 kA | 65 kA | not rated |
| FIL (current-limiting) | 20-100 A | 600 V | 200 kA | 200 kA | 100 kA |
| KAL | 70-250 A | 600 V | 42 kA | 25 kA | 22 kA |
| KHL | 70-250 A | 600 V | 65 kA | 35 kA | 25 kA |
| KCL | 110-250 A | 480 V | 100 kA | 65 kA | not rated |
| KIL (current-limiting) | 110-250 A | 600 V | 200 kA | 200 kA | 100 kA |
The catalog number matters more than the family name. A 240 V class FAL interrupts 10 kA; the 600 V class FAL of the same amp rating interrupts 18 kA at 480 V. On a study, the difference between reading the frame label and reading the full catalog number is the difference between a pass and a mislabeled bucket.
Square D: modern PowerPact replacements
| AIC class | Example types | AIC @ 240 V | AIC @ 480 V | AIC @ 600 V |
|---|---|---|---|---|
| D | HDL, JDL | 25 kA † | 18 kA | 14 kA |
| G | HGL, JGL | 65 kA | 35 kA | 18 kA |
| J | HJL, JJL | 100 kA † | 65 kA | 25 kA |
| L | HLL, JLL | 125 kA † | 100 kA | 50 kA |
| R | HRL, JRL | 200 kA † | 200 kA | see catalog |
Eaton / Cutler-Hammer: Series C F-frame
| Frame | Amps | Max voltage | AIC @ 240 V | AIC @ 480 V | AIC @ 600 V |
|---|---|---|---|---|---|
| EHD | 15-100 A | 480 V | 18 kA | 14 kA | not rated |
| FD | 10-225 A | 600 V | 65 kA | 35 kA | 18 kA † |
| HFD | 15-225 A | 600 V | 100 kA | 65 kA | 25 kA † |
| FDC | 15-225 A | 600 V | 200 kA | 100 kA | 35 kA † |
| HMCP (motor circuit protector) | 3-150 A | 600 V | combination-rated | 65 kA | combination-rated |
The HMCP row deserves a note because it is the one engineers misread most. A motor circuit protector is a magnetic-only device UL-recognized as a component of a combination starter, not a stand-alone listed breaker. Its usable interrupting rating is the tested combination rating with the specific starter in the bucket, which is why Eaton publishes most HMCP ratings in the starter tables rather than the breaker tables.
GE: E150, F225, and J600 lines
| Frame | Amps | Max voltage | AIC @ 240 V | AIC @ 480 V | AIC @ 600 V |
|---|---|---|---|---|---|
| TED4 | 10-150 A | 480 V | 18 kA | 18 kA | not rated |
| TED6 | 15-150 A | 600 V | 18 kA | 18 kA | 14 kA |
| THED | 15-150 A | 600 V | 65 kA | 25 kA | 18 kA |
| TFJ / TFK | 70-225 A | 600 V (3P) | 25 kA | 22 kA | 18 kA |
| THFK | 70-225 A | 600 V | 65 kA | 25 kA | 18 kA |
| TFL | 70-225 A | 600 V | 100 kA | 65 kA | 25 kA |
| TJK4 / TJJ | 125-400 A | 600 V | 42 kA | 30 kA | 22 kA |
| TJK6 | 250-600 A | 600 V | 42 kA | 30 kA | 22 kA |
| THJK4 / THJK6 | 125-600 A | 600 V | 65 kA | 35 kA | 25 kA |
Siemens: Sentron ED frame
| Type | Amps | Max voltage | AIC @ 240 V | AIC @ 480 V | AIC @ 600 V |
|---|---|---|---|---|---|
| ED2 | 15-125 A | 240 V | 10 kA | not rated | not rated |
| ED4 | 15-125 A | 480 V | 65 kA | 18 kA | not rated |
| ED6 | 15-125 A | 600 V | 65 kA | 25 kA | 18 kA |
| HED4 | 15-125 A | 480 V | 100 kA | 42 kA | not rated |
| HHED6 | 15-125 A | 600 V | 100 kA | 65 kA | 18 kA |
| CED6 | 15-125 A | 600 V | 200 kA | 200 kA | 100 kA |
Why this matters at replacement
Available fault current at the bucket stab is a property of the system, not the breaker, and it has generally risen over the life of a facility as utility services and transformers were upgraded. A breaker adequately rated when the lineup shipped in 1985 can be under-rated in the same slot today. The fastest failure mode on a study is the quiet one: a standard-tier FAL or TED in a bucket on a bus that now sees 30 kA available.
Every feeder bucket we build ships with a 65 kAIC breaker as standard, at or above the interrupting rating of nearly every legacy frame in these tables, so the replacement unit is never the weak point of the study. Buckets are built in our UL 508A panel shop and configured by lineup, height, and rating: configure a replacement. For replacement breakers themselves, including THED, FDC, and HMCP units for legacy buckets, see repair parts.