Breaker Interrupting Ratings (AIC) in Legacy MCC Buckets

UL interrupting ratings, kA RMS symmetrical, for the frames that actually live in 20 to 50 year old lineups. Compiled from manufacturer catalog documents, cited under each table.

Technical reference

Every fault-current study, arc-flash label, and bucket replacement runs into the same question: what can the breaker in that unit actually interrupt? The frames in legacy MCC buckets span decades of catalogs, several corporate acquisitions, and a naming system where one letter changes the interrupting rating by a factor of three. The ratings below are UL interrupting capacities in kA RMS symmetrical, compiled from the manufacturer documents cited under each table.

How to read the families: each manufacturer tiers the same physical frame by interrupting capacity. Square D encodes the tier in the second letter (FAL standard, FHL high, FCL extra-high, FIL current-limiting). Eaton/Cutler-Hammer prefixes the F-frame (FD standard, HFD high, FDC extra-high). GE uses TED to THED, TFJ/TFK to THFK, TJK to THJK. Siemens steps ED4/ED6 to HED4 to CED6. Two breakers that look identical in the bucket can differ by 80 kA of interrupting capacity, which is why the study needs the exact catalog number, not the frame name.

Square D: F-frame (100 A) and K-frame (250 A)

Source: Schneider Electric Digest, Circuit Breakers section DE3, CSA/UL Certified Interrupting Rating selection tables. Note that FCL and KCL carry no 600 V rating: an FCL in a 600 V class lineup is a misapplication regardless of its 65 kA rating at 480 V.
TypeAmpsMax voltageAIC @ 240 VAIC @ 480 VAIC @ 600 V
FAL (240 V cat.)15-100 A240 V10 kAnot ratednot rated
FAL (FAL34xxx)15-100 A480 V25 kA18 kAnot rated
FAL (FAL36xxx)15-100 A600 V25 kA18 kA14 kA
FHL15-100 A600 V65 kA25 kA18 kA
FCL15-100 A480 V100 kA65 kAnot rated
FIL (current-limiting)20-100 A600 V200 kA200 kA100 kA
KAL70-250 A600 V42 kA25 kA22 kA
KHL70-250 A600 V65 kA35 kA25 kA
KCL110-250 A480 V100 kA65 kAnot rated
KIL (current-limiting)110-250 A600 V200 kA200 kA100 kA

The catalog number matters more than the family name. A 240 V class FAL interrupts 10 kA; the 600 V class FAL of the same amp rating interrupts 18 kA at 480 V. On a study, the difference between reading the frame label and reading the full catalog number is the difference between a pass and a mislabeled bucket.

Square D: modern PowerPact replacements

Source: Schneider catalog 0611CT1001, PowerPact H-, J-, and L-Frame Circuit Breakers, and se.com datasheets (HDL36100, HGL36100, HJL36100, HLL36100). H-frame covers 15-150 A, J-frame 150-250 A. † 240 V values are standard catalog figures pending direct confirmation against 0611CT1001; the 480 V and 600 V columns are datasheet-verified.
AIC classExample typesAIC @ 240 VAIC @ 480 VAIC @ 600 V
DHDL, JDL25 kA †18 kA14 kA
GHGL, JGL65 kA35 kA18 kA
JHJL, JJL100 kA †65 kA25 kA
LHLL, JLL125 kA †100 kA50 kA
RHRL, JRL200 kA †200 kAsee catalog

Eaton / Cutler-Hammer: Series C F-frame

Sources: Eaton technical data TD01203013E (Series C F-Frame) and eaton.com product data for FD3100, HFD3110, FDC3100, EHD1100; HMCP data per Eaton Vol. 4, CA08100005E. † 600 V values sourced from Eaton spec data as republished by authorized distributors. HMCP interrupting ratings other than the 480 V figure are published as combination ratings with the starter they protect, which is how UL lists them.
FrameAmpsMax voltageAIC @ 240 VAIC @ 480 VAIC @ 600 V
EHD15-100 A480 V18 kA14 kAnot rated
FD10-225 A600 V65 kA35 kA18 kA †
HFD15-225 A600 V100 kA65 kA25 kA †
FDC15-225 A600 V200 kA100 kA35 kA †
HMCP (motor circuit protector)3-150 A600 Vcombination-rated65 kAcombination-rated

The HMCP row deserves a note because it is the one engineers misread most. A motor circuit protector is a magnetic-only device UL-recognized as a component of a combination starter, not a stand-alone listed breaker. Its usable interrupting rating is the tested combination rating with the specific starter in the bucket, which is why Eaton publishes most HMCP ratings in the starter tables rather than the breaker tables.

GE: E150, F225, and J600 lines

Source: GE BuyLog Catalog, Section 6, Molded Case Circuit Breakers Quick Reference Guide (UL File E-11592). In the J600 line the trailing 4 or 6 is the frame ampacity (400 vs 600 A), not the voltage class; both are 600 V rated. THED 110-150 A units carry 42 kA at 240 V.
FrameAmpsMax voltageAIC @ 240 VAIC @ 480 VAIC @ 600 V
TED410-150 A480 V18 kA18 kAnot rated
TED615-150 A600 V18 kA18 kA14 kA
THED15-150 A600 V65 kA25 kA18 kA
TFJ / TFK70-225 A600 V (3P)25 kA22 kA18 kA
THFK70-225 A600 V65 kA25 kA18 kA
TFL70-225 A600 V100 kA65 kA25 kA
TJK4 / TJJ125-400 A600 V42 kA30 kA22 kA
TJK6250-600 A600 V42 kA30 kA22 kA
THJK4 / THJK6125-600 A600 V65 kA35 kA25 kA

Siemens: Sentron ED frame

Source: Siemens Molded Case Circuit Breakers, ED-Frame Sentron Series datasheet, order no. CPDS-ED123-0520, UL 489 AIR interrupting ratings table.
TypeAmpsMax voltageAIC @ 240 VAIC @ 480 VAIC @ 600 V
ED215-125 A240 V10 kAnot ratednot rated
ED415-125 A480 V65 kA18 kAnot rated
ED615-125 A600 V65 kA25 kA18 kA
HED415-125 A480 V100 kA42 kAnot rated
HHED615-125 A600 V100 kA65 kA18 kA
CED615-125 A600 V200 kA200 kA100 kA

Why this matters at replacement

Available fault current at the bucket stab is a property of the system, not the breaker, and it has generally risen over the life of a facility as utility services and transformers were upgraded. A breaker adequately rated when the lineup shipped in 1985 can be under-rated in the same slot today. The fastest failure mode on a study is the quiet one: a standard-tier FAL or TED in a bucket on a bus that now sees 30 kA available.

Every feeder bucket we build ships with a 65 kAIC breaker as standard, at or above the interrupting rating of nearly every legacy frame in these tables, so the replacement unit is never the weak point of the study. Buckets are built in our UL 508A panel shop and configured by lineup, height, and rating: configure a replacement. For replacement breakers themselves, including THED, FDC, and HMCP units for legacy buckets, see repair parts.

Ratings above are compiled from the manufacturer documents cited under each table. Values marked † came from manufacturer spec data republished by authorized distributors rather than a catalog PDF we opened directly, and are flagged for that reason. Always verify against the breaker label and current manufacturer data before relying on a rating in a study.