NEMA Starter Ratings: Sizes 00-9

Ratings per NEMA ICS 2-2000 Tables 2-4-1 and 2-4-3 as reprinted in manufacturer catalogs, with overload trip classes, thermal unit selection rules, and cross-manufacturer class designations. Sources numbered at the end.

Technical reference

1. Ratings, three-phase, full-voltage single-speed controllers

NEMA ICS 2-2000 Table 2-4-1, limited plugging and jogging duty. Reprinted in Rockwell 500-TD014D pp. 3-4 (sizes 00-8) and Square D Type S catalog p. 13 (sizes 00-7); Size 9 per Allen-Bradley Bulletin 509 catalog p. 1-35. A circulating claim of 35 HP at 230 V for Size 3 is wrong; both manufacturer reprints of the NEMA table give 30 HP.
SizeContinuous AService-limit AHP 200 VHP 230 VHP 460 VHP 575 V
009111.51.522
018213355
127327.57.51010
2455210152525
39010425305050
41351564050100100
527031175100200200
6540621150200400400
7810932n/a300600600
812151400n/a450900900
92250n/an/a80016001600

Service-limit current, per ICS 2 paragraph 2-321.20: the maximum rms current the controller is permitted to carry for protracted periods in normal service, at temperature rises above the continuous-rating test values. The overload relay current rating, or trip current of other protective devices used, shall not exceed the service-limit current of the controller.

2. Plugging and jogging duty derate

The derated table applies when duty involves more than five openings or closings per minute, or more than ten in a ten-minute period: plug-stop, plug-reverse, or jogging service (ICS 2 footnote as printed in both catalogs; Eaton A200 catalog cites the rule as NEMA ICS 2-321). Sizes 7 through 9 carry no published jog or plug ratings. Square D publishes operation-rate limits for Size 6 and 7: 3 operations per minute continuous, 15 per minute for a maximum of 3 minutes under jogging or plugging duty.

NEMA ICS 2-2000 Table 2-4-3. Effect: jogging or plugging service moves the application up one size. A 25 HP, 460 V jog application requires Size 3; its standard-duty rating alone would allow Size 2.
SizeHP 200 VHP 230 VHP 460 VHP 575 VStandard-duty HP 460 V, for comparison
00111.51.52
01.51.5225
1335510
27.510151525
31520303050
425306060100
56075150150200
6125150300300400

3. Overload relay trip classes

IEC definition and bands: ABB publication 1SXU106043B0201. All classes: no trip at 1.05x setting current; trip within 2 hours at 1.2x. NEMA/UL frames the same classes as maximum trip time in seconds at 600% of trip rating. Setting current is motor nominal current, not trip current.
ClassDefinition (IEC 60947-4-1)Trip band at 7.2x setting currentSelection
10A / 10Max 10 s at 7.2x Ie4-10 sLow-inertia loads that must not stall long; A-B eutectic: J heater element
20Max 20 s at 7.2x Ie6-20 sDefault for general purpose motors; A-B eutectic: W heater element
30Max 30 s at 7.2x Ie9-30 sHigh-inertia starts; A-B eutectic: WL element; Square D slow-trip SB series
5-30 electronicProgrammableper settingRockwell E300: class 5-30, trip at 120% FLA; Eaton C440: 10A/10/20/30; A-B SMP: 10/15/20/30

4. Thermal unit (heater) selection rules, Square D melting alloy

Square D, Overload Relays and Thermal Unit Selection, 5/98, pp. 19-21. Example from the Schneider Digest: Size 1, motor FLA 17.0 A, SF 1.15: thermal unit B32, trip rating 16.0 x 1.25 = 20.0 A.
ConditionSelection
BasisMotor nameplate full-load amps. NEC/HP-derived values only as tentative fallback when the nameplate is unavailable.
Assumed ambientMotor and controller both at 40 C or less. Selection tables assume this.
Service factor 1.15-1.25100% of nameplate FLA
Service factor 1.090% of nameplate FLA
Controller 10 C hotter than motor locationMultiply selection FLA by 0.9 (SF 1.15-1.25) or 0.8 (SF 1.0)
Controller 10 C cooler than motor locationMultiply by 1.05 (SF 1.15-1.25) or 0.95 (SF 1.0)
Ambient-compensated bimetallic1.0x (SF 1.15-1.25) or 0.9x (SF 1.0), independent of controller ambient
Slow-trip Class 30 (Type SB)Select from standard Type B table at 93% FLA (SF 1.15-1.25) or 84% (SF 1.0), substitute SB prefix. Available sizes 0-2 and some Size 3.
Wye-delta (Class 8630)Divide delta-connected FLA by 1.73 before selection
Trip current rating125% of the minimum FLA listed for the selected thermal unit

5. Manufacturer class designations

Sources: Square D Type S catalog 5/98; Rockwell 500-TD014D and Bulletin 505/509 catalogs; GE Control Catalog Section 1 (CR306: nonreversing, non-combination, NEMA 00-5, 600 V max); Eaton A200 catalog and Freedom series Vol. 5 CA08100006E; Siemens NEMA starter brochures.
ManufacturerContactorFVNR starterReversingCombinationOther
Square D (Type S)Class 8502Class 8536Class 8736 (contactors 8702)8538/8539 (fusible/CB); reversing 8738/87398810/8811/8812 multispeed; 8630 wye-delta; 8640 part-winding
Allen-BradleyBulletin 500Bulletin 509 (sizes 00-9)Bulletin 505512 (fusible), 513 (CB)502/503/506/507 enclosed and combination variants
GECR305 / CR385CR306 (00-5), CR386 (6-9)CR309CR307/CR308/CR310/CR311
Eaton / Cutler-HammerA201; Freedom CN15/CN55A200 (00-9); Freedom AN16A210, A250 (sizes 5-9); Freedom AN56A900 two-speed
SiemensClass 14 (ESP200 overload)Class 22

6. Device data by size

Rockwell 500-TD014D pp. 3-6, Bulletin 500/509 line, 2-3 pole AC coil values; 4-5 pole coils run higher. Coil operating range 85-110% of rated voltage (both Rockwell and Square D). Closing inrush includes DC offset. n/p: not published. Neither ICS 2 nor the catalogs publish a single electrical-life figure for NEMA starters; Rockwell publishes AC-3/AC-4 load-life curves per IEC 947-4 test conditions instead, so treat any flat electrical-life claim as unsupported.
SizeMech. life, operationsPickup / dropout, msCoil inrush / sealed VA (60 Hz)Max closing inrush, A peak
0010,000,00020 / 1670 / 887
010,000,00021 / 16192 / 29140
110,000,00022 / 14192 / 29288
210,000,00027 / 13240 / 29483
35,000,00037 / 20660 / 45947
45,000,00027 / 201225 / 691,581
55,000,00025 / 181490 / 963,163
65,000,00025-79 / 10-224860 / 2546,326
7n/p88 / 40DC coil, control transformer fed9,470
8n/p88 / 45DC coil, control transformer fed14,205

Sources

1. NEMA ICS 2-2000, Tables 2-4-1 and 2-4-3, paragraph 2-321.20 (table identities per NEMA errata memo, May 2002; values via manufacturer reprints below).
2. Rockwell Automation publication 500-TD014D-EN-P, NEMA Contactor and Starter Specifications, March 2023.
3. Square D, Type S Contactors and Starters, Class 8536/8502/8736/8702/8810/8811/8812 catalog, 5/98.
4. Square D, Overload Relays and Thermal Unit Selection, 5/98.
5. Allen-Bradley Bulletin 509 catalog pages 1-33 to 1-35; Bulletin 505 catalog 505-CT003.
6. ABB publication 1SXU106043B0201, Thermal Overload Relays, Tripping Class 20.
7. Rockwell publication 193-TD006, E300/E200 Electronic Overload Relay Specifications.
8. GE Control Catalog, Section 1, NEMA Full Voltage Power Devices.
9. Eaton Cutler-Hammer A200 catalog (Jan 2006); Freedom series, Vol. 5 CA08100006E.

Related: VFD feeder sizing, unit height by amperage, renewal parts.